SmartVue™ Specifications
One Device. Endless Applications.
Physical & Environmental
Physical / Operational
- Case color: Black
- Dimensions: 3.6” (90 mm) High × 4.7” (119 mm) Wide × 4.8” (123 mm) Deep
- Weight: 1.04 lbs (580 g)
- Input Power Range 10 – 30 VDC, reverse polarity protected (external fuse recommended)
- Power Consumption (no load): < 1 A
- Power Consumption (max load): < 1.5 A
Panel Mount Info
- Bolt Pattern: Identical to EMM620 Panel Meter – see Mounting Pattern Drawing for details.
- Mounting Kit Accessories: Pan head Phillips screws (for various panel thicknesses) – 6/32 x 1/2″ (4), 6/32 x 5/8″ (4), 6/32 x 3/4″ (4)
Environmental
- Operating Temperature Range: -40F to +158F (-40°C to +70°C)
- Storage Temperature Range: -40F to +176F (-40°C to +80°C)
- Relative Humidity: 0 to 95%, non-condensing
- Vibration: 4.4G, 3 axis, frequency swept 5-2000 Hz
- Emissions Compliance: FCC part 15 Class A, Industry Canada
- NEMA4 weatherproof panel-mount design
- Class I Div. 2 (CSA/UL) Hazardous Location Compliance
Operational Specs
Protocols
- Modbus ASCII, RTU, TCP
- J1939
Communication Interfaces
- RS-232, RS-485
- Ethernet
Current Loop Inputs
2 Dedicated 16-bit, 4-20 mA
- Isolation: 500 Volts
- High frequency analog filtering
Analog Outputs
2 14-bit linear (isolated) analog outputs
- 4-20 mA up to 33 V max., or output for PID control
2 14-bit voltage outputs
- 0 – 10 V with 100Ω output impedance
- Maximum current of 10 mA
2 Frequency outputs
- 0.00 Hz – 6250 Hz
Multipurpose I/O
6 Multipurpose I/O, configured as DI, DO,or VI
- Digital Inputs:
- 0-30 VDC
- Configurable pull-up
- Adjustable threshold voltage
- Digital Outputs:
- 0-30 VDC
- Configurable pullup
- Open collector
- Output rating – 70mA max (hold), 140mA trip 1A peak, 50Ω impedance
- Voltage Inputs:
- 12bit with full scale 0 – 25 VDC
- 100kΩ impedance
Hardware Counters
6 Multipurpose I/O, configured as DI, DO,or VI
- 2Tachometers, 80,000 Counts/second
- 3Counters, 300,000 Counts/second
- Configurable as 2 quadrature encoders
RTD Sensor Channel
116-bit (non-isolated) RTD
- Pt 100 or 500 Ω DIN, IEC
- Measurement range: -328°F to +1562°F (-200 to +850 °C)
Modbus
- Modbus Slave communications over RS-232/485
- Supports Modbus RTU and Modbus ASCII protocols
- Support for Function Codes 2 & 4
- User configurable register mapping for all Process & Control Process data
- Includes preassigned registers for J1939 SPN & DTC data
Data Logging
- 450 MB data storage, > 14 million data points
- Selectively log process, control, I/O, J1939 data
- Configurable sampling period: 1 second to 24 hours
- Auto file/log creation on power up or config. change
- User configurable sequence names
- Export data to USB (CSV format)
- User configurable export – complete data sequence or time interval subset
- Overwrite (looping) feature for continuous logging
- J1939 diagnostic trouble codes stored separately
J1939
- 16 selectable J1939 parameter display screens
- Support DM1 active diagnostic codes
- Support for PGN requests
- Support VIN requests
- ISOBUS support
- Ability to disable transmit
- Fixed and arbitrary addressable
User-Configurable
- Inputs mapped to outputs
- Control Loops: PID, signal conversion/ retransmission
- Threshold triggers, latching or momentary
- Direct output control from touchscreen
Ready to Try SmartVue™?